Fujitronic Programmable Operation Display UG520H-x Manuel d'utilisateur Page 140

  • Télécharger
  • Ajouter à mon manuel
  • Imprimer
  • Page
    / 275
  • Table des matières
  • MARQUE LIVRES
  • Noté. / 5. Basé sur avis des utilisateurs
Vue de la page 139
2 - 71
Port
19200bps
Odd
8
Baud Rate
Parity
Transmission
Code
Data Length
Stop Bit 1
Response Delay Time
Function
Time-out
ASCII/HEX
Item Setting of PLC
1
19200bps
Odd
8
1
Comm. Parameter of POD
"0" for x 10, "1" for x 1
Host link system (fixed)
0 (fixed)
None (fixed)
HEX (fixed)
25 Koyo PLC
Communication Setting
The recommended communication parameter setting of both PLC and POD is as follows:
Available Memory
SU/SG , SU/SG(K-Sequence)
SR-1T/SR-T (K prt)
Set the memory to the extent of the memory range of each PLC model.
Use TYPE number to assign indirect memory for macro programs.
Memory TYPE Remarks
R(data register) 0
I (input relay) 1
Q(output relay) 2
M(internal relay) 3
S(stage) 4
GI (global inputs) 5
GQ (global outputs) 6
T(timer/contact) 7
C(counter/contact) 8
Memory TYPE Remarks
D(data register) 0
X (input relay) 1 X/Y common use
Y(output relay) 2 X/Y common use
M(internal relay) 3
S(stage) 4
K (keep relay) 5
L (link relay) 6
T(timer/contact) 7
C(counter/contact) 8